Home >

Products

>Combined Transformer Substation

Sanbian Sci-Tech Co., Ltd.

Chat View basket

Combined Transformer Substation

Description:

1.Summary
ZBW series combined power distribution station is the power distribution equipment combining high voltage transformer.transformer and low voltage equipment that is used for city tall buildings urban&rural buildings,residence communities,medium&small factories,mines,oil fields and temporary electrical power consuming sites. The station function to receive and distribute power energy in power distribution system.
ZBW series combined transformer features compact structure,package unit,safe and reliable operation,convenient maintenance,attractive apperance,bigh mobility and small size.It can be used as loop network power distribution system.It is a new set of equipment for urban&rural transformer substation construction and drenovation.
ZBW series combined substation complies with the standards of GB/T17467-1998 High Voltage/Low Voltage Pre-Installed Transformer substation and IEC1330.
2.Technical Parameters
2.1 High Voltage Switch Panel Parameter Table
Series NoName Unit Parameter
1Nominal voltagekV12
2Nominal frequencyHz50
3Nominal currentA630
4Nominalshort withstanding currentkA/2S20
5Nominal short peak currentkA50
6Withstanding current when grounding switch is closed for a short timekA/2S20
7Peak current when grounding switch is closed for a short timekA50
85% nominal on/off currentA31.5
9Nominal load on/off currentA630
10Drifting currentA1400
11Idle transformer on/off current A16
12Fuse combination switch short-circuit on/off currentkA/2S20
13On/off currentkA50
141 min power frequency withstand voltage ground,inter-phase/isolation notchkV effective value42/48
15Impulse withstand voltage ground,inter-phase/isolation notchkV effective value75/852.2 Transformer Main Technical Parameter Table
Type Nominal voltage(Kv)Nominal capacitance(kVA)
S9-M, S11-M6,1050-1600
SC9 SC10 SG106,1050-16002.3 Fuse Parameter Table
Type Nominal voltage(kV)Nominal on/off current(kA)Fuse nominal current(A)Fuse specific current(A)
SFLDJ
SFLAJ 1231.5406.3 10 16 20 25 31.5 40
10050 63 80 100
125125
40200160 200 Combined Transformer Substati

Do you want view original page?